SIVACON 8PT Low Voltage Switchgear
1. Product Overview
SIVACON 8PT which has the standard structure used in construction industry and industry technical field is one of the newest low-voltage switchgear designed by Siemens. It can be applied to every capacity grade with maximum current to 7400A. The installation methods include: Fixed installation, Plug-in installation and withdrawable installation. Meanwhile the 8PT has passed type test, therefore, it can ensure reliable operation and safety of personnel.
2. Overall Features
The low volt switch cabinet passes the type test(TTA)
Horizontal bus is arranged on the top of the switchgear.
Rated current of 3 electrode and 4 electrode horizontal bus system can be to 7400A’
Rated peak withstand current (IPK) can be to 375KA.
The size of the chamber is big enough to meet the requirements of every installation.
The chambers can be divided in different units according to modulus structure.
There is Single installation and Back to back installation.
Outgoing cable can be connected from front or back side of switchgear.
There is economical efficiency due to flexible solutions.
3. Design approach Introduction
Fixed-mounted technology(OFF)
Features: Lower-costs, highly safety. This kind of power distribution cabinet is mainly used in the places where changing is not needed or short-time power-off is allowed during working conditions.
Reactive power compensation(PFC)
Features: Lower-costs, highly safety. According to different kinds of Electrical equipment’s structure, Control cabinet can be equipped with a non-choke-type or choke-type capacitor components
3NJ6 Bar plug-in technology(OFPD)
Features: Support easy-plug, highly safety. Compared with withdrawable technology, power distribution cabinet with plug-in technology used in cable branch circuit is more economy. Its structure is compact and it can realize fast refitting or exchanging during working condition by incoming side plug-in contact. SICACON bar structure is more economy, safe and flexible.
For freedom of design of the control cabinet(CCS)
Features: have more flexible space. Variety of expansion elements can be chosen for freedom design and regulating cabinets. There are chambers inside the cabinet.
Plug-in design(OFPM)
Features: Support easy-plug, highly safety. Equipped with motor circuit and cable feeder circuits, the plug-in switchgear which is more economy is the replacement of withdrawable switchgear. The unit can realize fast exchanging by incoming side plug without power-off. Plug-in design is more economy, reliable and common.
Volume density is high (each cabinet can have up to 22 circuits).
Unplug design(OFW)
Features: Better applicability, highly safety. Equipped with motor circuit and cable feeder circuits, withdrawable switchgear has optimal safety and applicability and is easy to operate. Fast exchanging and regulation can be realized through guiding withdrawable mechanism. Each module can proceed such as addition or exchanging, even compartment can be exchanged during operation. Withdrawable unit is designed according to 8 kinds of modulus height (100,150, 200, 300, 400, 500, 600, 700mm).
4. Technical Data
standards and norms |
Low voltage complete switchgear passed TTA (TTA) Internal arc fault condition test |
IEC60439-1,DINEN60439-1(VDE0660 Part 500),IEC61641,VDE0660c Part 500 |
|
Air gap and creepage distances |
Rated impulse withstand voltage(Uimp) |
8KV |
|
Overvoltage category |
III |
||
Pollution level |
3 |
||
Rated insulation voltage(Ui) |
1000V |
||
Rated operating voltage(Ue) |
To 690V |
||
Rated Current(In) horizontal bus(3 electrode and 4 electrode) |
main bus-bar |
Rated Current |
to 7400A |
Rated peak withstand current(Ipk) |
to 375KA |
||
Rated short time withstand current(Icw) |
to 150KA,1S |
||
to 120KA,3S |
|||
Vertical bus technology for circuit breaker |
Rated Current |
to 6300A |
|
Rated peak withstand current(Ipk) |
to 250KA |
||
Rated short time withstand current (Icw) |
to 100KA,1S |
||
to 80KA,3S |
|||
Fixed mounted for vertical busbar design |
Rated Current |
to 1400A |
|
Rated peak withstand current(Ipk) |
to 163KA |
||
Rated short time withstand current (Icw) |
to 65KA*,1S |
||
to 50KA,3S |
|||
Vertical bus bar with strip technology (plug-in) (3NJ6) |
Rated Current |
to 2100A |
|
Rated peak withstand current(Ipk) |
to 110KA |
||
Rated short time withstand current (Icw) |
to 50KA*,1S |
||
Plug-in designed and withdrawable designed vertical busbar |
Rated Current |
to 1200A |
|
Rated peak withstand current(Ipk) |
to 163KA |
||
Rated short time withstand current (Icw) |